Friday, March 19, 2010

8 Honeywell S7800A Keyboard Display Modules from DtiCorp.com

Honeywell S7800A for Valve Proving provides current status of burner sequence, timing information, hold information and lockout information, as well as selectable or preemptive messages.


Fort Lauderdale, FL - Popular Honeywell online retailer DtiCorp.com (http://www.DtiCorp.com) is introducing 8 brand new Honeywell S7800A Keyboard Display Modules (KDM).


DESCRIPTION

Provides current status of burner sequence, timing information, hold information and lockout information, as well as selectable or preemptive messages.

The KDM provides local or remote annunciation of operation and fault information, remote reset, report generation, burner control data and diagnostic information. The KDM is part of the 7800 SERIES of microprocessor-based burner controls for gas, oil, coal or combination fuel single burner applications.
The 7800 SERIES is programmed to provide a level of safety, functional capabilities and features beyond the capacity of conventional controls.


FEATURES

• Application flexibility.
• Communication interface capability with Switchover to ModBus programmable.
• First-out annunciation and system diagnostics provided by 2 row by 20 column Vacuum Fluorescent Display (VFD).
• S7800A1001 offers "Call Service" (Business Card)programmable message displayed when system lockout occurs.
• S7800A1001 series 5 and greater has selectable ModBus Feature.
• Local or remote annunciation of operation and fault information.
• First out expanded annunciation with 24 limit and interlock LEDs enhances keyboard display module information. Display can be Programmed to customize the expanded annunciator messages to the system. Provides burner controller data.
• Remote reset.
• Report generation.

SPECIFICATIONS

The S7800A1001 KDM Series 5 offers the following technical advancements to the 7800 SERIES devices:
. Compatible with installed Honeywell 7800 SERIES systems.
. A three screen two-row by twenty-column readout set of
.Call Service. (Business Card) alpha/numeric directions can be displayed instead of the standard lockout display message. (Pass Code protected feature). This .business card. can be cloned to other displays to save setup time.
. Enable ModBus Communication feature.

The Business Card (Call Service) can be made up using:
. Capital letters (A through Z).
. Lower case letters (a through z).
. Numbers (1 through 0).
. Symbols (!, @, #, $,%, etc.).
. Spanish symbols.

Programming can be done with the S7800 KDM mounted on a 7800 SERIES Relay Module or with a 13 Vdc power source connected to the KDM through the 203541 5-wire connector. Since your Business Card (Call Service) S7800A1001 will be left at the job site, programming your personal three-number password and personal lockout message can be set up ahead of time without being connected to a 7800 SERIES device. A clone function allows you to make multiple Business Cards from the original display.


Models available:

1. S7800A1001 Keyboard Display-English

2. S7800A1035 Keyboard Display-French

3. S7800A1043 Keyboard Display-German

4. S7800A1050 Keyboard Display-Italian

5. S7800A1068 Keyboard Display-Spanish

6. S7800A1118 Keyboard Display-Katakana(Japanese)

7. S7800A1126 Keyboard Display-Portuguese

8. S7800A1142 Keyboard Display-English with Valve Proving, Postpurge, "Call Service", and Expanded Annunciator programming ability


About Us: DtiCorp.com (http://www.DtiCorp.com) carries more than 35,000 HVAC products, including industrial, commercial and residential parts and equipment from Honeywell, Johnson Contols, Robertshaw, Jandy, Grundfos, Armstrong and more. Our online catalog is easy to navigate and search, and all products have a picture and a description. If a customer has any questions about a product, they can call 800-757-5999 and speak with one of our product experts. Our mission is to offer the best prices anywhere to our customers.


Julian Arhire
Manager DtiCorp.com
Phone: 954.298.2515
Fax: 954.206.0767
Web: http://www.DtiCorp.com

###
DtiCorp.com, Honeywell, Keyboard Display Module, KMD, S7800A1001, S7800A1068, S7800A1142

Tuesday, March 9, 2010

DtiCorp.com is introducing 16 Honeywell L4006 Aquastat Controllers

Fort Lauderdale, FL - Popular Honeywell online retailer DtiCorp.com (http://www.DtiCorp.com) is introducing 16 Honeywell L4006 Aquastat Controllers.


DESCRIPTION

Aquastat® Controllers are immersion type devices for limiting or regulating the temperature of liquids in boilers, storage tanks, and other applications where temperature control is required.

FEATURES

• Totally enclosed Micro Switch™ snap-acting switches operate on temperature rise to setpoint.
• Visible control point scale and external adjustment screw permit easy setting.
• Horizontal or vertical insertion of the sensing element.
• Direct or well immersion of the sensing element.
• Models available for strap-on mounting.
• Remote bulb model may be used to sense air temperature in ducts and in outside air sensing applications.
• TRADELINE models include heat-conductive compound.
• Select models have wells.

SPECIFICATIONS

• Description: High or Low limit Aquastat Controller with 100 F to 240 F operating temperature and 5 F fixed differential
• Application: High or Low limit
• Bulb Size (in.): 3/8 in. x 2 7/8 in. copper
• Bulb Size (mm): 10 mm x 73 mm copper
• Well Spud Size (in.): 1/2 in. NPT
• Well Spud Size (mm): 13 mm NPT
• Capillary Length (in.): 1 1/2 in.
• Switching Action: SPST, contacts break on temperature rise.
• Operating Temperature Range (F): 100 F to 240 F
• Operating Temperature Range (C): 38 C to 116 C
• Electrical Ratings (millivolt): 0.25 A @ 0.25 to 12 Vdc
• Electrical Ratings (Full Load): 5.1A @ 240 Vac; 8A @ 120 Vac
• Electrical Ratings (Locked Rotor): 30.6A @ 240 Vac; 48A @ 120 Vac
• Electrical Ratings (AFL): 8A @ 120 Vac
• Electrical Ratings (AFL): 5.1A @ 240 Vac
• Electrical Ratings (ALR): 48A @ 120 Vac
• Electrical Ratings (ALR): 30.6A @ 240 Vac
• Differential Temperature (F): 5 F Fixed
• Differential Temperature (C): 3 C fixed
• Maximum Ambient Temperature (F): 150 F
• Maximum Ambient Temperature (C): 66 C
• Case Dimensions (in.): 5 5/8 in. high x 2 in. wide x 2 1/8 in. deep
• Case Dimensions (mm): 143 mm high x 51 mm wide x 54 mm deep
• Mounting: Horizontal or Vertical
• Approvals, Underwriters Laboratories Inc: UL Component Recognized File No. MP466, Vol. 6, Sec.1, Guide No. MBPR2
• Approvals, Canadian Standards Association - Certified: File No. LR95329-1
• Approvals, American Gas Association IAS: AGA Certified
• Includes: 1/2 in. well - 123869A
• Capillary Length (mm): 38 mm

Models available:

1. L4006A1009 High or Low limit Aquastat Controller with 100 F to 240 F operating temperature and 5 F fixed differential
2. L4006A1017 High or Low limit Aquastat Controller with 100 F to 240 F operating temperature and 5 F to 30 F adj. differential
3. L4006A1132 High or Low limit Aquastat Controller with 100 F to 240 F operating temperature and 5 F fixed differential
4. L4006A1678 High or Low limit Aquastat Controller with 100 F to 240 F operating temperature and 5 F to 30 F adj. differential
5. L4006A1959 High or Low limit Aquastat Controller with 100 F to 240 F operating temperature and 2 F fixed differential
6. L4006A1967 High or Low limit Aquastat Controller with 100 F to 240 F operating temperature and 5 F to 30 F adj. differential
7. L4006A2007 High or Low limit Aquastat Controller with 100 F to 240 F operating temperature and 5 F to 30 F adj. differential
8. L4006B1007 Circulator Aquastat Controller with 100 F to 240 F operating temperature, 5 F fixed Differential
9. L4006B1155 Circulator Aquastat Controller with 100 F to 240 F operating temperature, 5 F to 30 F adj. Differential
10.L4006B1163 Circulator Aquastat Controller with 100 F to 240 F operating temperature, 5 F to 30 F adj. Differential
11.L4006E1067 High Limit; Manual Reset Aquastat Controller with 130 F to 270 F operating temperature
12.L4006E1091 High Limit; Manual Reset Aquastat Controller with 130 F to 270 F operating temperature
13.L4006E1109 High Limit; Manual Reset Aquastat Controller with 130 F to 270 F operating temperature
14.L4006E1117 High Limit; Manual Reset Aquastat Controller with 100 F to 240 F operating temperature
15.L4006E1125 High Limit; Manual Reset Aquastat Controller with 100 F to 200 F operating temperature
16.L4006H1004 High Limit strap-on mounting Manual Reset Aquastat Controller with 100 F to 240 F operating temperature



About Us: DtiCorp.com (http://www.DtiCorp.com) carries more than 35,000 HVAC products, including industrial, commercial and residential parts and equipment from Honeywell, Johnson Contols, Robertshaw, Jandy, Grundfos, Armstrong and more. Our online catalog is easy to navigate and search, and all products have a picture and a description. If a customer has any questions about a product, they can call 800-757-5999 and speak with one of our product experts. Our mission is to offer the best prices anywhere to our customers.


Julian Arhire
Manager DtiCorp.com
Phone: 954.298.2515
Fax: 954.206.0767
Web: http://www.DtiCorp.com

###
DtiCorp.com, Honeywell, Aquastat Controller, L4006E1125, L4006H1004, L4006A1009