Thursday, January 8, 2015

Honeywell u2 series now certified to ktl compliance standards



Fort
Lauderdale, FL
- Honeywell announced that the U2
Series family of part numbers are now certified to KTL (
Korean Testing Laboratory) compliance
standards.

KTL
is a certification for Korea that operates as a testing and certification
company. It provides testing, assessment and quality on product safety,
reliability, performance and standards.

KTL
certification is the latest endeavor to ensure Honeywell Industrial Flame
Monitoring products continue to meet the various needs and standards globally. U2
units with the KTL certification are available now.


Models:

- U2-1010 - UV Tron/IR/UVSS - Quick disconnect cable.
Suitable for all fuels.
- U2-1010-PF
- UV Tron/IR/UVSS - Factory installed cable. Suitable for all fuels.
- U2-1012
- IR Quick disconnect cable. Suitable for oil and coal.
-
U2-1012-PF - IR Factory installed cable. Suitable for oil and coal.
- U2-1016
- UVTron - Quick disconnect cable. Suitable gaseous fuels.
-
U2-1016-PF - UVTron - Factory installed cable. Suitable gaseous fuels.
- U2-1018
- UVTron/IR - Quick disconnect cable. Suitable for all fuels.
-
U2-1018-PF - UVTron/IR - Factory installed cable. Suitable for all fuels.

The U2 Series
is an all-in-one integrated processor and viewing head system which is uniquely
suited for single or multi-burner, multi-fuel and difficult flame detection
applications. The all-in-one solution eliminates the need for a separate
processor which saves on cabinets and wiring. Multiple models and sensor
options meet difficult flame monitoring applications requiring a high level of
discrimination.

Features:

- Electronic
check (no mechanical shutter) for self-check of the system.
- Independent
configuration and adjustable gain settings for each sensor.
- Ten
selectable flicker frequency filters for solid state UV and IR sensor (model
dependent).
- Fully
programmable using touch screen interface with easy to follow scrolling menu
structure.
- Modbus
RS422 communication for use with FlameTools-PC or FlameTools-HMI/U supports 248
loops and 32 loops, respectively.

Specifications:

- Input
power: 22-26 VDC, 120 mA max.
- Output
relay contacts: one normally open flame relay and one normally open fault/self-check
relay, 2A, 30 VDC or 250 VAC.
- Ambient
temperature: -40°F to 158°F (-40°C to 70°C).
- Analog
flame signal: 0-20 mA or 4-20 mA output.
- Enclosure:
IP66 and NEMA 4X.
- Adjustable
flame on/off threshold.
- Adjustable
FFRT 1, 2, or 3 seconds.
- 1"
NPT mounting.
- Not
adversely affected by x-rays and gamma rays.

Approvals:

- FM, CSA,
INMETRO, pending EN 298 & KTL
- PF
version: Class I div 1 Gr A, B, C, D, E, F, G T6 – NEMA 4X, IEC Ex FMG 13.0023X
Ex d IIC T6 Gb IP66
- Quick
disconnect version: Class I div 2 Gr A, B, C, D T5 - NEMA 4X, IEC CSA13.0023 Ex
nA nC IIC T5 Gc IP66
- Fit for
use in SIL 3 applications

About Us: DtiCorp.Com
carries more than 35,000
HVAC products, including
industrial, commercial and residential parts and equipment from Honeywell,
Johnson Contols, Robertshaw, Jandy, Armstrong and more. Our online catalog is
easy to navigate and search, and all products have a picture and a description.
If a customer has any questions about a product, they can call and speak with
one of our product experts. Our mission is to offer the best prices anywhere to
our customers.




More
information about Honeywell U2-1010:

http://www.dticorp.com/catalog/honeywell-u21010-combination-viewing-head-and-signal-processor-p-160705.html