Restoring Factory Configuration
Introduction
This pr...



Restoring Factory Configuration For Honeywell UDC3200 Controllers.




This procedure restores the configuration of the instrument back to
the Factory Settings per Section “Error! Reference source not found.”




ATTENTION: Restoring the factory configuration overwrites all user-entered configuration changes.




This procedure cannot be undone, it is a one-way process.




=================== Restoring Factory Configuration ===================




What to do:


1. Turn off the power to the instrument for at least five seconds.


2. Turn the power back on and simultaneously press the “SETUP” and UP
keys. This must be done while “TEST DONE” is being displayed.


3. If step 2 was performed correctly, the instrument will now display “UDC” [Upper] “UPDATE” [Lower].


4. Press the Function Key. The instrument will now display “DIS” [Upper] “RESTORE” [Lower].


5. Press the UP key. The instrument will now display “CFG” [Upper] “RESTORE” [Lower].


6. Press the Function Key. The instrument will now display “DOIN” “RESTORE”


7. When the instrument finishes the restore operation, it
automatically resets itself and restarts in the product mode. The
instrument configuration will now be the same as it was when the
instrument left the factory and all user- entered configurations since
that time have been overwritten.