Showing posts with label Microprocessor Relay Module. Show all posts
Showing posts with label Microprocessor Relay Module. Show all posts

Wednesday, May 13, 2009

Honeywell RM7800 Microprocessor Relay Modules




Honeywell RM7800E, G, L, M Relay Modules
Microprocessor-based integrated burner control for automatically fired gas, oil, coal or combination fuel single burner applications. Provides safety, functional capability and features beyond conventional controls.
APPLICATION

The Honeywell RM7800 is a microprocessor based integrated
burner control for automatically fired gas, oil or combination
fuel single burner applications. The RM7800 system consists
of a Relay Module and Keyboard Display Module, Subbase,
Amplifier, and Purge Card. Options include Personal
Computer Interface, DATA CONTROLBUS MODULE™,
Remote Display Mounting, First-Out Expanded Annunciator
and Combustion System Manager¨ Software.
The RM7800 is programmed to provide a level of safety,
functional capability and features beyond the capacity of
conventional controls.
Functions provided by the RM7800 include automatic burner
sequencing, flame supervision, system status indication,
system or self-diagnostics and troubleshooting.

FEATURES
• Safety features:
— Interlock check.
— Closed loop logic test.
— Dynamic AMPLI-CHECK™.
— Dynamic input check.
— Dynamic safety relay test.
— Dynamic self-check logic.
— Expanded safe-start check.
— High Fire Purge Switch test.
— Internal hardware status monitoring.
— Low Fire Start Switch test.
— Tamper resistant timing and logic.
• Access for external electrical voltage checks.
• Application flexibility.
• Provides 0.8 to 3.0 second Flame Failure Response
Time (FFRT), depending on amplifier selected.
• Communication interface capability.
• Dependable, long-term operation provided by
microcomputer technology.
• First-out annunciation and system diagnostics
provided by 2 row by 20 column Vacuum Fluorescent
Display (VFD) located on the Keyboard Display
Module.
• First-out expanded annunciation with 26 Light Emitting
Diodes (LEDs) for limits and interlocks (optional).
• Five sequence information LEDs
• Five function Run/Test Switch.
• Interchangeable plug-in flame amplifiers.
• Local or remote annunciation of operation and fault
information (optional).
• Nonvolatile memory for retaining history files and
sequencing status after loss of power.
• Remote reset (optional).
• Report generation (optional).
• Burner controller data:
— Sequence status.
— Sequence time.
— Hold status.
— Lockout/alarm status.
— Flame signal strength.
— Expanded annunciator status.
— Total cycles of operation.
— Total hours of operation.
— Fault history of six most recent faults:
• Cycles of operation at time of fault.
• Expanded annunciator data at time of fault.
• Fault message and code.
• Hours of operation at time of fault.
• Sequence status at time of fault.
• Sequence time at time of fault.
— Diagnostic information:
• Device type.
• Flame amplifier type.
• Flame failure response time.
• Manufacturing code.
• On/Off status of all digital inputs and outputs.
• Selected prepurge time.
• Software revision and version of RM7800 and
Keyboard Display Module.
• Status of configuration jumpers.
• Status of Run/Test Switch.
SPECIFICATIONS
Electrical Ratings, see Table 1:
Voltage and Frequency: 120 Vac (+10/-15%),
50 or 60 Hz (+/- 10%)4.
Keyboard Display Module: 13 Vdc peak full wave rectified
(+20/-15%).
Power Dissipation:
RM7800: 10 Watts maximum.
Display Module: 3 Watts maximum.
Maximum Total Connected Load: 2000 VA.
Fusing: Total Connected Load: 20A maximum, type FRN
or equivalent.
Environmental Ratings:
Ambient Temperature:
Operating: -40°F to 140°F (-40°C to 60°C).
Storage: -40°F to 150°F (-40°C to 66°C).
Humidity: 85% RH continuous, noncondensing.
Vibration: 0.5G environment.
Weight:
RM7800: 1 pound 13 ounces, unpacked.
Keyboard Display Module: 4 ounces, unpacked.
Approval Bodies:
Underwriters Laboratories Inc. listed, File No. MP268,
Guide No. MCCZ.
Canadian Standards Association certified, LR9S329-3.
Factory Mutual approved, Report No. J.I.1V9A0.AF.
IRI acceptable.
Federal Communications Commission, Part 15,
Class B—Emissions.
Mounting: Q7800A for panel mount or Q7800B for wall
or burner mount.
Required Components:
Plug-in Flame Signal Amplifier, see Table 2.
ST7800A Plug-in Purge Timer Cards: selectable models:
two seconds to 30 minutes.
Q7800A or Q7800B Wiring Subbase.